SWA as the CPC
steel wire armour as the earth conductor
SWA as CPC? - Terminating the cable ends of SWA cables.
| Article Index |
|---|
| SWA as CPC? |
| page 2 |
| page3 |
| All Pages |
Terminating the cable ends of SWA cables.
BS7671 has a fundamental requirement set out in regulation 133-01-04 for every electrical joint and connection shall be of proper construction as regards conductance, insulation, mechanical strength and protection.
This requirement would preclude the termination of the cable ends of SWA with bonding clamps for the reason given above. It would also preclude the termination of the cable by inserting it into an enclosure without a gland as the steel armouring earth continuity could not be reliable.
Cable manufacturers supply and recommend the termination of their SWA cables in glands correctly selected for the individual size of the particular cable. These glands are supplied for internal use and alternative exterior glands rated at IP66 for external use.
The manufacturer’s gland kits are provided with suitably sized earth rings which are commonly known as “Banjos”. These earth rings are used to enhance the contact surface area of the gland and are also provided with a bolt hole for connection of an auxiliary CPC.
The cable glands can be directly used without the earth ring in the same manner as conduits and MICC cables are terminated in metal enclosures. As with conduits and MICC cables the paint around the enclosure hole must be removed to expose bare metal. The gland lock nuts must then be suitably tightened to maintain conductivity.
Some enclosures are provided with removable gland plates and in these circumstances the earth continuity relies on the gland plate fixing screws. It is recommended in these circumstances that the earth ring is used with a suitably sized CPC connected to the main earth bar. This is never done with conduit or MICC in my experience which also relies on these fixing screws for earth continuity. An alternative would be to drill the gland plate and bolt a CPC to it connected to the main earth bar.
where an SWA cable enters a plastic enclosure then an earth ring would be needed to maintain earth continuity.
It goes without saying that the steel wires of the armouring should all enter the tapered socket of the cable gland and the gland nut should be adequately tightened.
In the same way as the regulations do not require a separate CPC to be used with metal conduits it would seem good practice to always use an earth ring. This ring to be separately bolted to the enclosure and a CPC with a crimped eyelet connected to this bolt. The CPC then connected to the earth terminal of the enclosure. If the enclosure is outside or exposed to moisture then it would be preferable to place the earth ring on the inside of the enclosure. This will permit the paint or other coating to be removed under the ring without compromising the environmental protection for the enclosure.
Environmental Conditions
There is a general requirement for all electrical equipment to be suitable for the environmental conditions prevailing for that installation set out in BS7671. There is also an additional requirement for earthing systems set out in 542-01-07 which requires, “ they are adequately robust or have additional mechanical protection appropriate to the assessed conditions of external influence”.
I have found one reference in IEE GN7 that would preclude the use of the armouring as a CPC when SWA cables are used. This is in Marinas and the guidance states, “Due to the possibility of corrosion, the galvanised steel armouring of cables must not be used wholly or in part as a circuit protective conductor (cpc) for the floating section of marinas. A separate protective conductor should be used which, when in accordance with Regulation 543-01-02 can be common to several circuits if necessary. The armour must still, however, be connected to protective earth”.
If the SWA cable ends are terminated outside or in areas where water is present then the exterior IP66 glands should be used.
TNCS (PME) Installations
Where the supply company will not permit the export of the means of earthing to the supplied premises outside of those premises then special precautions will need to be taken for SWAs supplying remote buildings or equipment outside the supplied premises.
The reason for this restriction is to prevent the danger of exposed conductive parts and extraneous conductive parts connected to the installation outside the main equipotential zone becoming live in the event of the loss of the neutral under fault conditions. Also with long cable runs their will be a potential difference between the supplied earth from the neutral terminal and the general mass of earth.
In these circumstances it is preferred to connect the steel armouring of the SWA to earth at the main supplied premises and insulate the armouring at the remote end of the cable. This allows the SWA cable to be protected by the circuit protection device that is protecting the phase conductor(s) of the cable. At the remote building the SWA is terminated in a plastic box and only the live conductors are then connected to the remote installation. The remote installation is converted to a TT system with a suitably selected RCD main switch and the provision of an earth electrode.
It may also be possible with the consent of the supply company to extend the main equipotential zone to the remote building. This can be done by using the SWA armouring as a combined CPC and main bonding conductor. All extraneous metal work in the remote building is connected to a common terminal known as the Building Earth Marshalling Terminal (BEMT). The armouring must be sized to comply both with Regulations 547-02-01 and 543-01. In addition with a PME system there may be currents flowing normally in the protective conductors which may raise the temperature of the SWA cable. In these circumstances the cable will need to be derated to accommodate this temperature rise. An alternative may be to run a parallel PVC green/yellow cable of suitable size with the SWA. If this parallel CPC is buries then it would need to be a minimum of 16mm2 to comply with Regulation 542-03-01 unless it is mechanically protected.
If the remote building has an alternative means of earthing then the SWA armour or separate CPC would need to be rated to permit the maximum current flow likely to comply with Regulation 542-01- 09.
Earth Loop Impedance
Where the measured value of earth loop impedance (Zs) at the end of a final circuit is found to be to high to achieve automatic disconnection by the circuit protection device in the required disconnection time Regulation 413-02-04 permits the use of supplementary bonding to achieve an acceptable measured value of Zs. This in my view is a compensatory measure for poor initial design of the circuit and incorrect selection of the cable. If the cable was correctly selected at the design stage with due regard to the required value of Zs for the final circuit, the Zs of the distribution board, the R1 + R2 calculated value for the size and length of cable and any temperature correction then compensatory measures would not be required. If supplementary bonding is required then the use of a spare core of an SWA cable could be used or an additional CPC run in parallel with the cable.
Supplementary CPCs.
Where it is determined that a selected cable size will not provide sufficient CSA for the CPC a supplementary CPC can be run in parallel with the SWA cable. This CPC should be adequately sized to handle the full potential earth fault current not just to provide sufficient additional capacity to the SWA armour to meet the required CSA. This is required as the currents flowing under fault conditions would not be equally distributed over the cables due to differences in impedance.
Conclusion
The use of internal cores, of both thermoplastic and thermosetting SWA cables, as a CPC and/or the use of separate parallel CPCs are not required for SWA cables to comply with BS7671 provided.
- The operating temperature of the cable does not exceed 700C.
- The CSA of conductor cores does not exceed 95mm2.
- The cable is not installed in the floating section of any marina.
- The cable is correctly selected for the correct value of R1 + R2 for the circuit protection device protecting the cable.
- The cable does not connect different installations together which have separate means of earthing unless sized for the potential earth fault current.
- The cable is not used as a combined CPC and bonding conductor on a PME installation unless suitably sized.
- The cables are properly terminated in correctly sized manufactures brass glands selected for the external influences prevailing.
- Where a removable gland plate is present on the enclosure to which the cable is attached the earth ring ( banjo) supplied with the gland is used and is connected to the earth terminal in the enclosure with a separate CPC. This CPC terminated in an eyelet to a bolted connection to the earth ring.
- Any protective coating on the enclosure surface is removed under the contact surfaces of the gland and associated earth ring to expose bare metal.
- All the wires of the armouring enter the gland and the gland nut is adequately tightened. The cable is adequately supported up to the gland with cable cleats to prevent mechanical strain on the gland.
References
- BS 7671:2001 amended to 2004 Requirements for Electrical Installations.
- IEE Guidance Note 1 Selection and Erection.
- IEE Guidance Note 7 Special Locations.
Thanks to: ©John Peckham 2006